Main features of the Fluke 1760 three-phase recorder

  • Class A compliance: Perform tests according to the strict international IEC 61000-4-30 Class A standard.
  • GPS synchronization: Accurately relates recorded data and events with a standardised time reference.
  • Flexible and fully configurable thresholds and scaling factors: Allows the user to analyse specific problems by defining detailed criteria for disturbance detection and recording.
Check the lead time with Edimar.

Available on backorder

28.355,00 € excluding VAT - 34.309,55 € including VAT

Available on backorder

✓ This product supports 3% welcome discount. Conditions

Quantity
    EAN: 0095969348249 SKU 2637634 Categories , Brand:
    MPN: 2637634
    Fluke

    Share this product:

    Description

    Specifications of the Fluke 1760TR three-phase power quality logger

    Summary of measurement functions

    • Statistical evaluation: Electrical quality statistics according to EN50160 and DISDIP tables such as ITIC, CEBEMA, ANSI.
    • Event list: Fluctuations and interruptions are detected and stored. Triggers are also stored as events.
    • Continuous logging: RMS values, transients and fast transients for voltage, current, power (P, Q, S), power factor, kWh, voltage flicker, unbalances, frequency, harmonics and interharmonics.
    • Triggered logs (RMS): Adjustable interval between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3 s (150/180 cycles).
    • Oscilloscope: Sampling rate of 10,24 kHz for the 8 channels.
    • Fast transients: Selectable sampling rate between 100 kHz and 10 MHz for the FFT function from channel 1 to 4.
    • Online mode: Variable update rate for quick setup and event summary.

    General data

    • Intrinsic uncertainty: Refers to reference conditions and has a 2 year warranty.
    • Quality system: Developed according to ISO 9001: 2000.

    Environmental conditions

    ParameterRange
    Operating temperature rangeFrom 0 °C to +50 °C (32 °F to 122 °F)
    Power-on temperature rangeFrom -20 °C to +50 °C (-4 °F to 122 °F)
    Storage temperature rangeFrom -20 °C to +60 °C (-4 °F to 140 °F)
    Climatic classB2 (IEC 654-1), -20 °C to +50 °C (-4 °F to +122 °F)
    Maximum altitude2.000 m max. at 600 V CAT IV¹, power supply: 300 V CAT III

    Power supply

    • AC: from 83 V to 264 V, 45 to 65 Hz
    • DC: from 100 V to 375 V
    • Power consumption: NIMH, 7,2 V, 2,7 Ah
    • Battery pack: Internal battery with 40 minutes autonomy in case of power failure.

    Display and LED indicators

    • Power LED to indicate power supply.
    • Three-colour LED indicators per channel for overload and minimum load conditions.

    Memory and interfaces

    • Data memory: 2 GB Flash memory.
    • Interfaces: Ethernet (100 MB/s), RS 232.

    Dimensions and weight

    • Dimensions: 325 x 300 x 65 mm (2,8 x 11,8 x 2,6 in.)
    • Weight: Approximately 4,9 kg (10,8 lb) without accessories.

    Warranty

    • Warranty: 2 years
    • Calibration interval: 1 year recommended for class A, otherwise 2 years.