Fluke 1673 SCH FTT

Out of stockOut of stock

Fluke 1673 multifunction installation tester + Fluke TrueTest Advanced Software

Main features

  • Simple bidirectional user interface without complex multi-level menus
  • Easy configuration via full-colour touchscreen, smart device or PC
  • Fast and accurate testing thanks to automatic checking and automatic measurement validation
  • On-site preview of results and certificate generation with Fluke TruTest™️
  • No complicated data entry thanks to Fluke Connect compatibility

Contents:

  • Multifunction installation tester
  • High-performance power cable with single input connector
  • Hard case
  • USB-C power adapter for charging
  • Remote control probe
  • Carrying strap
  • Compensation adapter
  • Test leads and probes
  • Alligator clips
  • Lithium-ion battery
Check the lead time with Edimar.

Out of stock

2.297,00 € excluding VAT - 2.779,37 € including VAT

Out of stock

EAN: 0195112119624 SKU FLK 1673 SCHFTT Category Brand:
MPN: 1673 SCHFTT
Fluke

Share this product:

Description
General specifications
SpecificationFeatures
Size26,25 cm x 14,19 cm x 11,93 cm (10,3” x 5,6” x 4,7”)
Weight (including batteries)1,6 kg
Battery size and numberBP290, lithium-ion, 10,8 V, 2500 mAh, 27 Wh
Water resistanceIEC 60529: IP40
SafetyComplies with IEC/EN 61010-1, IEC 61010-2-030, IEC 61010-2-034 standards
Safety categoryCAT III 600 V, CAT IV 300 V
PerformanceIEC 61557-1 to IEC/EN 61557-8 and IEC 61557-10
AC, DC voltage and frequency measurement
RangeResolutionInput impedanceOverload protection
600 V0,1 V320 kΩ660 V
45 – 66 Hz0,1 Hz320 kΩ–
Continuity check (RLO)
Range (auto range)ResolutionOpen circuit voltage
20 Ω / 200 Ω / 2000 Ω0,01 Ω / 0,1 Ω / 1 Ω>4 V
Insulation resistance measurement (RISO)
Test voltages
1672100-250-500-1000 V
1673 FC / 1674 FC50-100-250-500-1000 V
Test voltageInsulation resistance rangeResolutionTest current
50 V10 kΩ to 50 MΩ0,01 MΩ1 mA to 50 kΩ
100 V10 kΩ a 20 MΩ 20 MΩ a 100 MΩ0,01 MΩ 0,1 MΩ1 mA to 100 kΩ
250 V10 kΩ a 20 MΩ 20 MΩ a 200 MΩ0,01 MΩ 0,1 MΩ1 mA to 250 kΩ
500 V10 kΩ a 20 MΩ 20 MΩ a 200 MΩ 200 MΩ a 500 MΩ0,01 MΩ 0,1 MΩ 1 MΩ1 mA to 500 kΩ
1000 V100 kΩ a 200 MΩ 200 MΩ a 1000 MΩ0,1 MΩ 1 MΩ1 mA to 1 MΩ
Insulation PreTest
Preliminary insulation safety checkConnections are required from the tester to L, N and PE.
Insulation PreTest; insulation ramp test of SPD (surge protective device) (varistor test) IEC 61643-11
Test voltageVoltage rangesResolutionTest currentAccuracy
500 VRamp in increments from 0 V to 500 V1 V1 mA± (1,5% + 3 digits)
1000 VRamp in increments from 0 V to 1000 V1 V1 mA± (1,5% + 3 digits)
 
Insulation Monitoring Devices (IMD) IEC 61557-8
RangeResolutionNote
1 kΩ to 10 kΩ1 kΩ>>1 MΩ only available with voltages >100 V
10 kΩ to 100 kΩ10 kΩ
100 Ω to 3 MΩ100 kΩ
Loop and line impedance (ZI without tripping and high current)
Range adjustmentResolutionAccuracy[1]
10 Ω[2]0,001 ΩHigh current mode in mΩ: ± (2% + 15 digits); no-trip mode (2 and 3 wires): ± (3% + 6 digits)
20 Ω0,01 ΩHigh current mode: ± (2% + 4 digits)
200 Ω0,1 ΩModo sin disparo: ± (3%) Modo de alta corriente: ± (2%)
2000 Ω1 Ω± 6%[3]
  1. Valid for neutral circuit resistances <20 Ω and a system phase angle of 30° maximum. Before testing, the test lead resistances must be zeroed.
  2. Fluke Connect™ 1674 FC model only.
  3. Valid for mains voltage >200 V.
Predicted Earth Fault Current (PEFC) Predicted Short-Circuit Current (PSC)
RangeResolutionUnits
0 kA to 50 kAIK <1000 A IK ≥1000 A1 A 0,1 kA
Calculation: The predicted earth fault current (PEFC/IK) or the predicted short-circuit current (PSC/IK) are determined by dividing the measured mains voltage by the measured loop (L-PE) or line (L-N) resistance, respectively. Voltage drop (via line impedance test)
RangeResolutionAccuracy
0,0-99,9%0,1%Tenga en cuenta la exactitud de las medidas de impedancia de línea
Note: The voltage drop reading is calculated from the line impedance measurement and the entered rated current. RCD tests, types of RCD tested
RCD type[1]16721673 FC1674 FC
AC[2]G[3]•••
ACS[4]•••
A[5], F[6]G•••
A, FS•••
B, B+[7]G••
B, B+S••
RCD-DD, RCD A/EV, RCD B/Mi[8]••
GFCI•••
 
  1. Inhibited RCD test for V >265 AC
  2. RCD tests only permitted if the product of the selected current and earth resistance is <50 V
  3. AC: Responds to AC
  4. G: General, no delay
  5. S: Time delay
  6. A: Responds to AC and pulsed signal
  7. F: Responds to AC, pulsed signal and high frequency
  8. B, B+: Responds to AC, pulsed signal, high frequency and smooth DC
  9. RCD-DD: Responds to residual currents of 6 mA DC
 
RCD trip time check (ΔT)
Test functionRCD current selection
10 mA30 mA100 mA[1]300 mA[1]500 mA[1]1000 mA[2]Var[3]
x½, 1•••••••
x5•••
Ramp•••••••
Automatic•••
Mains voltage 50 V – 265 V AC, 45/66 Hz
  1. Type B residual current devices require a mains voltage range from 195 V to 265 V.
  2. Residual current devices of type CA only.
  3. Type A residual current devices are limited to 700 mA; not available for type B devices.
Measurement/ramp test of RCD trip current (IΔN)
Current rangeStep sizeDwell timeMeasurement accuracy
Type GType S
From 30% to 110% of the RCD rated current[1]10% of IΔN[2]300 ms/step500 ms/step±5%
1. Specific trip current ranges (IEC 61008-1):
         De 30% a 150% para Tipo A IΔ N>10 mA De 30% a 210% para Tipo A IΔ N = 10 mA De 20% a 210% para Tipo B De 50% a 100% para Tipo CA De 35% a 140% para Tipo A (>10 mA) De 35% a 200% para Tipo A (£ 10 mA) De 50% a 200% para Tipo B2. 5% para Tipo B
Earth resistance test (RE) at 1673 FC and 1674 FC only
RangeResolutionFrequencyOutput voltage
200 Ω / 2000 Ω0,1 Ω / 1 Ω128 Hz25 V
Phase sequence indication
IconRangeDisplay
Phase sequence indicator is active185 V to 600 V“1-2-3”: or “3-2-1” if the phase is incorrect