{"id":2155,"date":"2024-09-24T12:18:46","date_gmt":"2024-09-24T12:18:46","guid":{"rendered":"https:\/\/electronicaedimar.com\/producto\/fluke-1736\/"},"modified":"2026-11-04T09:01:19","modified_gmt":"2026-11-04T07:01:19","slug":"fluke-1736","status":"publish","type":"product","link":"https:\/\/electronicaedimar.com\/en\/product\/fluke-1736\/","title":{"rendered":"Fluke 1736"},"content":{"rendered":"<h1>Specifications: Fluke 1736 and 1738 three-phase power quality loggers<\/h1>\n<h2>Specifications<\/h2>\n<table border=\"1\" cellpadding=\"10\" cellspacing=\"0\">\n<thead>\n<tr>\n<th>Parameter<\/th>\n<th>Range<\/th>\n<th>Resolution<\/th>\n<th>Intrinsic accuracy (% of reading + % of full scale)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Voltage<\/td>\n<td>1000 V<\/td>\n<td>0,1 V<\/td>\n<td>\u00b1 (0,2% + 0,01%)<\/td>\n<\/tr>\n<tr>\n<td>Corriente: entrada directa i17xx-flex 1500 12&#8243;<\/td>\n<td>150 A \/ 1500 A<\/td>\n<td>0,1 A \/ 1 A<\/td>\n<td>\u00b1 (1% + 0,02%)<\/td>\n<\/tr>\n<tr>\n<td>i17xx-flex 3000 24&#8243;<\/td>\n<td>300 A \/ 3000 A<\/td>\n<td>1 A \/ 10 A<\/td>\n<td>\u00b1 (1% + 0,03%)<\/td>\n<\/tr>\n<tr>\n<td>i17xx-flex 6000 36&#8243;<\/td>\n<td>600 A \/ 6000 A<\/td>\n<td>1 A \/ 10 A<\/td>\n<td>\u00b1 (1,5% + 0,03%)<\/td>\n<\/tr>\n<tr>\n<td>Clamp meter i40s-EL<\/td>\n<td>4 A \/ 40 A<\/td>\n<td>1 mA \/ 10 mA<\/td>\n<td>\u00b1 (0,7% + 0,02%)<\/td>\n<\/tr>\n<tr>\n<td>Frequency<\/td>\n<td>42,5 Hz to 69 Hz<\/td>\n<td>0,01 Hz<\/td>\n<td>\u00b1 (0,1%)<\/td>\n<\/tr>\n<tr>\n<td>Auxiliary input<\/td>\n<td>\u00b1 10 V CC<\/td>\n<td>0,1 mV<\/td>\n<td>\u00b1 (0,2% + 0,02%)<\/td>\n<\/tr>\n<tr>\n<td>Min.\/max. voltage<\/td>\n<td>1000 V<\/td>\n<td>0,1 V<\/td>\n<td>\u00b1 (1% + 0,1%)<\/td>\n<\/tr>\n<tr>\n<td>Voltage THD<\/td>\n<td>1000%<\/td>\n<td>0,1%<\/td>\n<td>\u00b1 0,5<\/td>\n<\/tr>\n<tr>\n<td>Current THD<\/td>\n<td>1000%<\/td>\n<td>0,1%<\/td>\n<td>\u00b1 0,5<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Intrinsic uncertainty<\/h2>\n<table border=\"1\" cellpadding=\"10\" cellspacing=\"0\">\n<thead>\n<tr>\n<th>Parameter<\/th>\n<th>Influence quantity<\/th>\n<th>iFlex1500-12<\/th>\n<th>iFlex3000-24<\/th>\n<th>iFlex6000-36<\/th>\n<th>i40S-EL<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Active power P<\/td>\n<td>FP \u2265 0,99<\/td>\n<td>1,2% + 0,005%<\/td>\n<td>1,2% + 0,0075%<\/td>\n<td>1,7% + 0,0075%<\/td>\n<td>1,2% + 0,005%<\/td>\n<\/tr>\n<tr>\n<td>Active energy Ea<\/td>\n<td>FP \u2265 0,99<\/td>\n<td>1,2% + 0,005%<\/td>\n<td>1,2% + 0,0075%<\/td>\n<td>1,7% + 0,0075%<\/td>\n<td>1,2% + 0,005%<\/td>\n<\/tr>\n<tr>\n<td>Apparent power S<\/td>\n<td>0 \u2264 FP \u2264 1<\/td>\n<td>1,2% + 0,005%<\/td>\n<td>1,2% + 0,0075%<\/td>\n<td>1,7% + 0,0075%<\/td>\n<td>1,2% + 0,005%<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Electrical specifications<\/h2>\n<ul>\n<li>Power supply: Voltage range from 100 V to 500 V using a safe input connector when powered from the measured circuit.<\/li>\n<li>Consumption: Maximum 50 VA.<\/li>\n<li>Efficiency: \u2265 68,2% (according to energy efficiency standards).<\/li>\n<li>Mains frequency: 50\/60 Hz \u00b1 15%.<\/li>\n<li>Battery: 3,7 V, 9,25 Wh lithium-ion, user-replaceable.<\/li>\n<li>Battery autonomy: Up to 5,5 hours in power-saving mode.<\/li>\n<\/ul>\n<h2>Environmental specifications<\/h2>\n<ul>\n<li>Operating temperature: -10 \u00b0C to +50 \u00b0C.<\/li>\n<li>Storage temperature: -20 \u00b0C to +60 \u00b0C.<\/li>\n<li>Operating humidity: Max. 95% RH.<\/li>\n<li>Operating altitude: 2000 m (up to 4000 m with reduced overvoltage category).<\/li>\n<\/ul>\n<h2>General specifications<\/h2>\n<ul>\n<li>Display: 4,3-inch colour LCD, active matrix resistive TFT touchscreen.<\/li>\n<li>Dimensions: 19,8 cm x 16,7 cm x 5,5 cm (instrument).<\/li>\n<li>Weight: 1,1 kg (instrument).<\/li>\n<li>Warranty: Instrument: Two years, accessories: One year.<\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<h1>Main features: Fluke 1736 and 1738 three-phase power quality loggers.<\/h1>\n<ul>\n<li>Versatile instruments compatible with Fluke Connect: Conduct electrical consumption studies, load analysis and power quality assessments.<\/li>\n<li>Key measurements: Automatically capture and record voltage, current, energy, harmonics and power quality values. Log current sags, swells and overloads with event waveform images and high-resolution true RMS profiles.<\/li>\n<li>Convenient instrument power supply: Direct power supply from the measured circuit.<\/li>\n<\/ul>","protected":false},"featured_media":2153,"comment_status":"open","ping_status":"closed","template":"","meta":{"_acf_changed":false,"_joinchat":[]},"product_brand":[139],"product_cat":[35,74],"product_tag":[],"class_list":["post-2155","product","type-product","status-publish","has-post-thumbnail","product_brand-fluke","product_cat-instrumentacion-electronica","product_cat-comprobadores-electricos","first","onbackorder","taxable","shipping-taxable","purchasable","product-type-simple"],"acf":[],"_links":{"self":[{"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/product\/2155","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/comments?post=2155"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/media\/2153"}],"wp:attachment":[{"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/media?parent=2155"}],"wp:term":[{"taxonomy":"product_brand","embeddable":true,"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/product_brand?post=2155"},{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/product_cat?post=2155"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/electronicaedimar.com\/en\/wp-json\/wp\/v2\/product_tag?post=2155"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}