  • Key measurements: Automatically capture and record voltage, current, power, power factor, energy and associated values.
  • Convenient instrument power supply: Power the instrument directly from the measured circuit.
  • Highest industry safety rating: 600 V CAT IV / 1000 V CAT III rating for use at the service entrance and downstream systems.
Check the lead time with Edimar.

Available on backorder

3.758,00 € excluding VAT - 4.547,18 € including VAT

Available on backorder

Quantity
    SKU FLUKE-1732 Categories , Brand:
    MPN: 4706594
    Fluke

    Share this product:

    Description

    Specifications: Fluke 1732 and 1734 three-phase electrical consumption loggers

    Specifications

    ParameterRangeResolutionIntrinsic accuracy (% of reading + % of full scale)
    Voltage1.000 V0,1 V± (0,2 % + 0,01 %)
    Corriente: entrada directa i17xx-flex 1500 12″150 A / 1.500 A0,1 A / 1 A± (1 % + 0,02 %)
    i17xx-flex 3000 24″300 A / 3.000 A1 A / 10 A± (1 % + 0,03 %)
    i17xx-flex 6000 36″600 A / 6.000 A1 A / 10 A± (1,5 % + 0,03 %)
    i40s-EL clamp4 A / 40 A1 mA / 10 mA± (0,7 % + 0,02 %)
    Frequency42,5 Hz to 69 Hz0,01 Hz± (0,1 %)
    Auxiliary input± 10 V CC0,1 mV± (0,2 % + 0,02 %)
    Min./max. voltage1.000 V0,1 V± (1 % + 0,1 %)
    Voltage THD1.000 %0,1 %± 0,5
    Current THD1.000 %0,1 %± 0,5

    Intrinsic uncertainty

    ParameterInfluence quantityiFlex1500-12iFlex3000-24iFlex6000-36i40S-EL
    Active power PFP ≥ 0,991,2 % + 0,005 %1,2 % + 0,0075 %1,7 % + 0,0075 %1,2 % + 0,005 %
    Active energy EaFP ≥ 0,991,2 % + 0,005 %1,2 % + 0,0075 %1,7 % + 0,0075 %1,2 % + 0,005 %
    Apparent power S0 ≤ FP ≤11,2 % + 0,005 %1,2 % + 0,0075 %1,7 % + 0,0075 %1,2 % + 0,005 %

    Electrical specifications

    • Power supply: Voltage range from 100 to 500 V when using a safety plug input when powered from the measurement circuit
    • Power consumption: Maximum 50 VA
    • Efficiency: ≥ 68,2 %
    • Input signal frequency: 50/60 Hz (from 42,5 to 69 Hz)

    Environmental specifications

    • Operating temperature: -10 °C to +50 °C
    • Storage temperature: From -20 °C to +60 °C
    • Operating humidity: Max. 95% RH
    • Operating altitude: 2000 m

    General specifications

    • Display: 4,3 inch colour LCD
    • Dimensions: 19,8 x 16,7 x 5,5 cm
    • Weight: 1,1 kg
    • Warranty: Instrument: Two years, accessories: One year